-
Error Codes for Sanden Heat Pump G4 GAU-A45HPC
The HP will display an error code if it is unable to function normally.
Error codes are indicated by a red LED on the control panel. The control panel is visible via a small window at the right side of the heat pump and it can be accessed by removing the heat pump top cover (4 screws).After a component is replaced or the inspection is completed, cycle power to the unit several times to confirm the error does not re-occur.
Below is the list of the error codes. If the corrective action does not solve the error problem, a malfunction of the PCB valve is highly likely.Error
code
Reason for the error
Corrective action
H9
HP ambient(outdoor)
temperature thermistor error
Check the thermistor connectors on the main PCB or control PCB in the heat pump unit for any disconnection, fall-off, wire breakage or short circuit.
Measure resistance of the thermistor indicated by the error code.
HC
HPwater outlet (outgoing)
temperature thermistor error
J3
HP discharge temperature
thermistor error
J5
HP suctiontemperature
thermistor error
J6
HP defrosttemperature
thermistor error
J8
HPwater inlet (return)
temperature thermistor error
H7
Tank temperature thermistor error
- Check the thermistor cable on the terminal block in the heat pump unit for any disconnection, fall-off, wire breakage or short circuit.
- Measure resistance of the thermistor indicated by the error code.
E6
Compressor bootingerror
- Check the compressor connector.
- Replace the main PCB or heat pump.
H6
Compressor revolution error
- Check the supply voltage.
- Measure resistance of each thermistor.
- Measure resistance of coil of expansion valve to check open or short circuit.
Error
code
Reason for the error
Corrective action
Replace the PCB or heat pump.
U0
Refrigerant leakageerror
- Measure resistance of each thermistor.
- Measure resistance of coil of expansion valve to check open or short circuit.
- Replace the main PCB or heat pump.
E1
Main PCB error
Replace the control PCB.
E2
L7
Control PCB error
Replace the control PCB.
F5
Communication error between main PCB to control PCB
- Check the communication connector on the main PCB and control PCB.
- Replace the main PCB or control PCB.
E8
High inlet current error
- Check the installation location.
- Check the supply voltage.
- Replace the main PCB or heat pump.
H8
Current error
Replace the main PCB.
L4
High temperature of module error
- Check the installation location.
- Remove foreign objects from the evaporator coil (e.g. fallen leaves, grass, snow).
- Check the fan motor is not flowing by dirt.
- Replace the main PCB or fan motor.
L5
High outlet current error
- Measure resistance of the discharged thermistor.
- Measure resistance of coil of expansion valve to check open or short circuit.
- Replace the main PCB or heat pump.
P4
Module temperature
thermistor error
Replace the main PCB.
U2
High voltage error
Check the supply voltage.
HJ
Water circuit error
- Check the inlet water valve.
- Check for any piping bend, blockage, kink or frozen.
- Measure resistance of each thermistor.
- Measure resistance of coil of expansion valve to check open or short circuit.
- Replace the main PCB or heat pump.
EC
High water outlet error
- Check the water circuit is not flowing by air, dirt or scaling.
- If the water circulation pump is not working, replace the pump.
- Measure resistance of water outlet (outgoing) thermistor.
- Replace the main PCB.
E9
Water circulation pump error
- Check the water is full in the tank.
- If the water circulation pump is not working, replace the pump.
- Check the revolution of pump by controller. If the revolution is low, replace the pump.
- Replace the main PCB.
Error
code
Reason for the error
Corrective action
E7
Fan motor locked
- Remove foreign objects around the fan motor.
- Check the fan motor connectors on the main PCB.
- Replace the main PCB.
F3
Discharged temperature error
- Measure resistance of the discharged thermistor.
- Replace the main PCB or heat pump.
Error
code
Reason for the error
Corrective action
H9
HP ambient(outdoor)
temperature thermistor error
Check the thermistor connectors on the main PCB or control PCB in the heat pump unit for any disconnection, fall-off, wire breakage or short circuit.
Measure resistance of the thermistor indicated by the error code.
HC
HPwater outlet (outgoing)
temperature thermistor error
J3
HP discharge temperature
thermistor error
J5
HP suctiontemperature
thermistor error
J6
HP defrosttemperature
thermistor error
J8
HPwater inlet (return)
temperature thermistor error
H7
Tank temperature thermistor error
- Check the thermistor cable on the terminal block in the heat pump unit for any disconnection, fall-off, wire breakage or short circuit.
- Measure resistance of the thermistor indicated by the error code.
E6
Compressor bootingerror
- Check the compressor connector.
- Replace the main PCB or heat pump.
H6
Compressor revolution error
- Check the supply voltage.
- Measure resistance of each thermistor.
- Measure resistance of coil of expansion valve to check open or short circuit.
Error
code
Reason for the error
Corrective action
Replace the PCB or heat pump.
U0
Refrigerant leakageerror
- Measure resistance of each thermistor.
- Measure resistance of coil of expansion valve to check open or short circuit.
- Replace the main PCB or heat pump.
E1
Main PCB error
Replace the main PCB.
E2
L7
Control PCB error
Replace the control PCB.
F5
Communication error between main PCB to control PCB
- Check the communication connector on the main PCB and control PCB.
- Replace the main PCB or control PCB.
E8
High inlet current error
- Check the installation location.
- Check the supply voltage.
- Replace the main PCB or heat pump.
H8
Current error
Replace the main PCB.
L4
High temperature of module error
- Check the installation location.
- Remove foreign objects from the evaporator coil (e.g. fallen leaves, grass, snow).
- Check the fan motor is not flowing by dirt.
- Replace the main PCB or fan motor.
L5
High outlet current error
- Measure resistance of the discharged thermistor.
- Measure resistance of coil of expansion valve to check open or short circuit.
- Replace the main PCB or heat pump.
P4
Module temperature
thermistor error
Replace the main PCB.
U2
High voltage error
Check the supply voltage.
HJ
Water circuit error
- Check the inlet water valve.
- Check for any piping bend, blockage, kink or frozen.
- Measure resistance of each thermistor.
- Measure resistance of coil of expansion valve to check open or short circuit.
- Replace the main PCB or heat pump.
EC
High water outlet error
- Check the water circuit is not flowing by air, dirt or scaling.
- If the water circulation pump is not working, replace the pump.
- Measure resistance of water outlet (outgoing) thermistor.
- Replace the main PCB.
E9
Water circulation pump error
- Check the water is full in the tank.
- If the water circulation pump is not working, replace the pump.
- Check the revolution of pump by controller. If the revolution is low, replace the pump.
- Replace the main PCB.
Error
code
Reason for the error
Corrective action
E7
Fan motor locked
- Remove foreign objects around the fan motor.
- Check the fan motor connectors on the main PCB.
- Replace the main PCB.
F3
Discharged temperature error
- Measure resistance of the discharged thermistor.
- Replace the main PCB or heat pump.
-
Why does the Sanden Eco® Plus use CO2 as its working gas? Isn’t CO2 a greenhouse gas and therefore harmful to the environment?
Why does the Sanden use CO2 as its working gas, what is the benefit?
- There is far less environmental impact (i.e. No ozone layer depletion and minimal global warming) than other commonly used refrigerants, should the system leak.
- There is a much higher efficiency, thereby allowing more heat to be transferred to the water, for less energy used (i.e. Excellent thermodynamic ability).
Isn't CO2 a greenhouse gas and therefor bad for the environment?
While it is true that Carbon Dioxide (CO2) is a greenhouse gas it has a Global Warming Potential (GWP) of 1. Whereas refrigerant gases in other heat pumps can have GWP of over 10,000, which means if they leak to the atmosphere they contribute 10,000 times more to global warming compared with the refrigerant gases used in a Sanden Eco Plus.
The table below shows the GWP for some common refrigerant gases (note: GWP must include a time interval over which the greenhouse gases act, in this case 100 years)
Our system utilizes less than 1 kg of R744 (CO2) as a refrigerant contained in a closed system at the factory. The installer does not need to charge the heat pump on site.
- There is far less environmental impact (i.e. No ozone layer depletion and minimal global warming) than other commonly used refrigerants, should the system leak.
-
Do I need to register my Sanden Eco Plus warranty?
-
What is the noise level of the Sanden Eco® Plus heat pump hot water system?
The unit is rated at 37dB (measured at one metre from the unit), which is almost silent. By comparison, a whisper is around 30dB and the sound of the inside of a Library is approximately 40dB.
-
Sanden Eco Hot Water Tank Size Options? Which tank size should I choose?
The Sanden Eco Plus hot heat pump hot water system is available in the following five sizes with our sizing guide below:
Tank size/shape Tank Code System No. of People No. of Bathrooms Dwelling type Off-peak & Continuous tariffs? Tank Diameter (mm) Tank Height (mm) 160L SS SAN-160SAQA GAUS-160FQTS 1 1 Bedsits Continuous only 621 970 250L SS
SAN-250SAQA GAUS-250FQTD 1-3 1-2 Residential Both 621 1428 250L SS Tall Slim SAN-250SAQD GAUS-250FQTD 1-3 1-2 Residential Both 580 1635 300L SS Tall Slim SAN-300SAQA GAUS-300FQTS 2-6 1-3 Residential Both 580 1891 300L SS Tall Slim SAN-300SAQD GAUS-300FQTD 2-6 1-3 Residential Both 580 1905 315L SS SAN-315SAQA GAUS-315FQTS 2-6 1-3 Residential Both 621 1748 315L SS Tall Slim SAN-315SAQD GAUS-315FQTD 2-6 1-3 Residential Both 580 2000 315L VE SAN-315VE GAUS-315FQTV 2-6 1-3 Residential Both 638 1626 *SS = Stainless Steel // VE = Vitreous Enamel
The same Sanden Heat Pump condenser unit is used in combination with different tanks sizes. So which tank size you would like?
When considering tank sizes - we need to consider a few factors - number of people, number of bathrooms, the heat recovery rate.
If you're using an existing hot water system for comparison - here are some comments/thoughts:
If you have an existing gas storage hot water system (e.g. 130L / 170L) - these are much smaller in capacity but they will reheat several times a day. Therefore the Sanden tank size will be larger than an existing gas storage replacement with the Sanden re-heat typically only required once per day - a good opportunity to maximise rooftop solar PV production or to utilise an off peak tariff.
If you have an existing electric storage hot water system (e.g. 400L 3.6kW unit) - these electric storage 3.6kW units recover heat at a slower rate (60L/hr) compared to a Sanden heat pump (approx. 80L/hr). Therefore a 400L electric storage hot water system would equate to a 300L/315L Sanden system in this example.
Based on our years providing the Sanden Eco heat pump hot water system - here are our tank recommendations for different scenarios (SS - Stainless Steel // VE - Vitreous Enamel):
160L SS: Only recommended for 1 person bedsits. This tank size is rarely chosen and due to its small tank size must be run in Continuous only mode (no blockout timer can be set up).
250L SS: Typically 1-3 person household with 1 bathroom. Height just under 1.5m with tank diameter 621mm.
250L SS Tall Slim: Typically 1-3 person household with 1 bathroom. Height just under 1.635m with tank diameter 580mm.
300L SS: The Tall Slim - the most popular and best recommended tank choice. Recommended for 2-6 people. Tank diameter 580mm and tank height just under 1.9m. If no height restrictions apply, this is the recommended tank for majority of situations and considered best value for money across the tank sizes.
315L SS: The largest tank size with an additional 15L delivered hot water (5% more) compared to the 300L Tall Slim tank. Tank diameter 621mm with tank height 1.74m - this is recommended if the 300L tall slim tank is too tall for your application.
315L SS Tall Slim: The largest tank size with an additional 15L delivered hot water (5% more) compared to the 300L. Tank diameter 580mm with tank height 2m - this is recommended if you're a very high hot water user.
315L VE: Tank diameter 638mm with tank height 1.63m with 315L delivered hot water. This VE tank is specified for poor water quality areas - you can identify if you are in a poor water quality area via the Sanden website -> https://www.sanden-hot-water.com.au/check-water-quality/
-
There is a red LED flashing on the Sanden heat pump display panel should I be worried?
The flashing red dot (LED) indicates the Sanden heat pump unit is currently in 'sleep mode', it is perfectly normal and nothing to worry about.
We consider this the "Sanden Heart Beat". If you see a red flashing dot, the heart is beating and all is well for your Sanden heat pump.
This controller display with the red flashing dot is applicable to the following Sanden heat pump models:
Sanden G3 - "GS3-45HPA-AU"
Sanden G4 - "GAU-A45HPC"
Sanden G5 - "GAU-A45HPD"
-
Uploading Photos for Sanden Eco Heat Pump Quote
Uploading Photos for Sanden Eco Heat Pump Quote
As heat pump hot water systems receive Government subsidies and rebates, Government authorities are requiring all photos are GEO-tagged to comply.
If you are unsure that your photos are GEO-tagged, we have a helpful Geo-tag guide on our website here -> https://pure-electric.com.au/resources/geo-tagging-helpful-guide
You can test if your photos are GEO-tagged by uploading photos to this website -> https://tool.geoimgr.com/
Please see below some photo tip examples for uploading photos to your Sanden Eco heat pump quote request.
Existing Hot Water System (Left)
Photo Tips: 2-3m to the left of the tank and up to the eaves
Existing Hot Water System (Right)
Photo Tips: 2-3m to the right of the tank and up to the eaves
Existing Hot Water System (Serial Number)
Photo Tips: Clear and readable
Switchboard
Photo Tips: Clear and readable so if you zoom in you can see the circuit breaker rating, enclosure flaps are open
Meterbox (Outline)
Photo Tips: Meterbox Door Open
Old Tank Details (Example filled in:)
Old Tank Make: Rheem
Old Tank Model: 315T136G
Old Tank Serial: 33633XXXX
Old Tank Date: 15/03/2006
If you have a renovation with a new hot water system location, please share a photo that confirms both hot and cold connections are presented:
-
At what temperatures will the Sanden Eco® Plus heat pump hot water system operate effectively?
The Sanden Eco Plus heat pump hot water (HPHW) system will operate effectively between - 10 º C and + 43 ° C, without the need for an electric booster element. It is also fitted with built in freeze protection, making it suitable for all climates.
-
What is the life expectancy of the Sanden Eco® Plus heat pump hot water system?
The Sanden Eco Plus heat pump hot water (HPHW) system is designed to last for 15 years. The high quality, weather resistant Eco® Plus HWHP outdoor module carries a 6 year warranty and the extra-long life stainless steel storage tank carries a class leading, 15 year warranty.
-
Sanden Heat Pump Hot Water Not Working
If you believe your Sanden Eco Heat Pump is not producing hot water, please try the following:
- Unless there is water pouring (not dripping) out of the unit, do not turn the unit off and on until you've checked the clock / control panel for an error message (under our "Resources" section you can find the different error code pages to help you determine what an error code looks like). If water is pouring out then turn the unit off at the isolator and at the switchboard that circuit is attached to.
- Pull the PTR Valve on the Tank - this confirms if there is hot water in the tank. If unsure about the water temperature use a thermometer. If water is cold goto (2) If there is 50C or so hot water in the tank then the problem is not the heat pump system) the problem is on the house side of the tank. So the tempering valve needs to be checked for a blockage / choke, if it is installed upside down or if it has failed (they are consumable items with a lifespan of 5-6 years and they fail to safe when they fail meaning cold water).
- Check the electricity supply - Confirm/check both (1) circuit breaker at the switchboard is ON + (2) Isolator at the HP unit is ON
- If you see a little Red Dot in the bottom right corner, then the HP unit has power connected. For the older G2 model 2010-2016 the dot is on the controller hidden under the lid - you will need a screwdriver to remove the 4 screws from the each end of the lid.
- Check if there are any Error Codes at the clock/computer control panel. If an error code is present, take note of the Error Code. Turn off the HP at the isolator (wait 1 minute) and turn on the HP again to see if the Error Code re-appears. The unit is functioning correctly if it blows cold air for more than 30minutes. NOTE: The unit takes about 7 minutes to start blowing cold air after power is applied.
- If system is newly installed or new plumbing works have occurred on site confirm that the tempering safety valve (valve with orange/yellow cap) is installed the right way up with a H on the vertical barrel above the adjustable valve and a C below the adjustable valve. If the system is more than 5 years old please note these valves officially only have a minimum life span of 5 years and may need replacing.
- Air bleed the system - Open the water drain plugs on the right hand side of the HP unit (one at a time for a good 3 minutes PER drain plug, ONE at a time). G4 units have an additional bleed port on the underside of the heat pump - please only turn this 180 degrees approx when opening it up - bleed this for 3 minutes also. Re-set the HP unit at the Isolator.
- Hard re-set the HP unit controller:
- Switch off power to the HP
- With power switched off press and hold down both “Up” and “Down” keys on the control panel simultaneously
- With the keys still pressed switch on power to the unit, the display will show “FClr” .... wait 10 seconds.
- To complete the reset cycle power to the unit off (wait 1 minute) and then on again.
- With power back on the time will be displayed (if required adjust to correct time) and the unit will run it's start up procedure.
- When switching power on again, the country setting "1.AU" may appear on the display. If for any reasons this setting remains on the display, simply press "Enter" and the Control Panel to confirm and HP will continue the start-up process.
- Physical inspection of the HP
- Turn off the electrical isolator, to allow power to discharge, wait 5 minutes after the power is turned off
- Take the top panel off by unscrewing the 4x screws
- Check to see if any debris/foreign objects are the top of the unit
- If an onsite plumber or electrician has a volt meter check for ~230VAC at the terminals on the side of the unit.
- If you have an older G2 unit and E124 is displaying then the unit has been subject to either high grid voltages or has suffered a power spike. Adding a timer to the switchboard and keeping the unit powered off for more than 19 hours per day can clear the fault for each and every use. This is successful in 50% of cases however works better where it is done the first time the error is ever seen. Not where the unit has been turned on and off many times.
- If you are getting E040 on an older G2 unit then you can clean the filter via the filter housing at the bottom of the unit adjacent the air bleed drain plugs. This may get you up and running again temporarily while you book a service. BOOK YOUR SERVICE OPTION HERE
- For blockages in newer units a 3 way ball valve can be installed which allows the consumer to perform their own reverse flush of the system. This maintenance step is normally part of a 4 year service can then be done annually just before the air bleed is performed.