Sanden Heat Pump Error Codes G3 GS3-45HPA-AU

Description

Sanden Heat Pump G3 GS3-45HPA-AU Error Codes

This is an excerpt from the PDF Sanden Heat Pump - Service Technical Manual Pages 33 -  50 for the error code summary for the Sanden Heat Pump G3 GS3-45HPA-AU.

"When an error has occurred, a red LED on the operation panel turns on and an error code is displayed on the LED display. The panel does not revert to the display sleep mode while the error code is shown.

After a component is replaced or the inspection is completed, turn the breaker OFF for a period of 3 minutes before restarting to confirm the error does not re-occur. Below is the list of the error codes. If the corrective action does not solve the error problem, a malfunction of the PCB is highly likely."

Error Code Example

Sanden Heat Pump G3 Error Code Example
Sanden Heat Pump G3 GS3-45HPA-AU Error Code Example

.

 

Error Code

 

Error Contents

 

Diagnostic

Check Points

 

Judgment & Repair Methods

Connector No. or

Maintenance Monitor No.

 

Connector Colour

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E001

 

 

 

 

 

 

 

 

 

 

 

 

 

HP water outlet over temperature 1

Error Detection Condition

When the hot water temperature thermistor detect 86  or more

<Check Items>

- Check dust being stuck on HP connector

 

 

- Remove dust if any

- Bends or blockings on HP connection pipes

 

 

-Correct piping and remove bends and

blockings

 

- freeze on pipes

 

 

- Melt the freeze if any and apply insulation

 

- Water valve is closed

 

 

 

- Open water valve

- Stopper valve is closed

 

 

- Open stopper valve

- confirm tank is filled

 

 

- fill tank with water if it

is not

 

 

 

 

- Water circulation pump malfunction

 

 

 

 

- if Water circulation pump do not start operating even after turning it on, on the operation panel, it is a malfunction of the Water circulation pump.

 

 

Error Code

 

Error Contents

 

Diagnostic

Check Points

 

Judgment & Repair Methods

Connector No. or Maintenance

Monitor No.

 

Connector Colour

 

 

 

 

 

 

 

 

 

 

 

 

E002

 

 

 

 

 

 

 

 

 

 

 

HP water outlet over temperature 2

Error Detection Condition Outlet water temperature error

<Check Items>

- Check dust being stuck on HP connector

 

 

 

- Remove dust if any

- Bends or blockings on HP connection pipes

 

 

-Correct piping and remove bends and blockings

 

- freeze on pipes

 

 

- Melt the freeze if any and apply insulation

- Water valve is closed

 

 

- Open water valve

- Stopper valve is closed

 

 

- Open stopper valve

- confirm tank is filled

 

 

- fill tank with water if it is not

 

 

- Water circulation pump malfunction

 

 

- if Water circulation pump do not start operating even after turning it on, on the operation panel, it is a malfunction of the Water

circulation pump.

 

 

 

 

E003

 

 

HP outlet temperature thermistor detection error

Error Detection Condition

When the hot water temperature thermistor didn't detect 30     or more during 30 minutes after the compressor operation start

<Check Items>

 

- Check if the hot water thermistor is fallen out

 

 

- Put the hot water thermistor back into the pocket on pipe if it is out.

 

 

 

 

 

 

 

 

 

 

 

 

E004

 

 

 

 

 

 

 

 

 

 

 

HP discharge over temperature 1

Error Detection Condition

When the discharge temperature thermistor detect 130  or more

<Check Items>

 

- malfunction of discharge temperature thermistor

 

CN500

 

White

 

- Replace discharge temperature thermistor

 

- Check if expansion valve connector is fallen out or not connected properly

 

 

CN504

 

 

White

 

- Put it back on properly if it is not in right position

 

 

- Check resistance between 2 phases on expansion valve coil (see table)

 

 

- Abnormal: Valve coil replacement required (together with PC board)

- Normal: Heat pump unit replacement required

 

- Blockage in refrigerant pipes

 

 

 

- Heat pump unit replacement required

 

 

Error Code

 

Error Contents

 

Diagnostic

Check Points

 

Judgment & Repair Methods

Connector No. or Maintenance

Monitor No.

 

Connector Colour

 

 

 

 

 

 

 

 

 

 

 

 

E005

 

 

 

 

 

 

 

 

 

 

 

HP discharge over temperature 2

Error Detection Condition Discharge temperature error

<Check Items>

- malfunction of discharge temperature thermistor

 

CN500

 

White

- Replace discharge temperature thermistor

- Check if expansion valve connector is fallen out or not connected properly

 

CN504

 

White

- Put it back on properly if it is not in right position

 

 

- Check resistance between 2 phases on expansion valve coil (see table)

 

 

- Abnormal: Valve coil replacement required (together with PC board)

- Normal: Heat pump unit replacement required

 

 

- Blockage in refrigerant pipes

 

 

 

 

- Heat pump unit replacement required

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E006

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HP discharge temperature Thermistor detection error

Error Detection Condition

When the discharge temperature thermistor didn't detect 45     or more during 30 minutes after the compressor operation start

<Check Items>

 

 

- Check if the discharge temperature thermistor is fallen out

 

 

 

CN500

 

 

 

White

 

 

- Put the dischrage temperature thermistor back into the pocket on pipe if it is out.

 

- Check if expansion valve connector is fallen out or not connected properly

 

 

CN504

 

 

White

 

- Put it back on properly if it is not in right position

 

 

 

 

- Check resistance between 2 phases on expansion valve coil (see table)

 

 

 

- Abnormal: Valve coil replacement required (together with PC board)

 

- Normal: Heat pump unit replacement required

 

- leakage on refrigerant pipes

 

 

 

- Heat pump unit replacement required

 

 

Error Code

 

Error Contents

 

Diagnostic

Check Points

 

Judgment & Repair Methods

Connector No. or Maintenance

Monitor No.

 

Connector Colour

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E007

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High pressure side error

Error Detection Condition

When high pressure switch open is detected

<Check Items>

- Check on HP connector

 

 

- Remove dust if any

- Bends or blockings on HP connection pipes

 

 

-Correct piping and remove bends and blockings

 

- freeze on pipes

 

 

- Check temperature on pipe cover that is exposed to ambient

temperature

- Water valve is closed

 

 

- Open water valve

- Stopper valve is closed

 

 

- Open stopper valve

- confirm tank is filled

 

 

- fill tank with water if it is not

 

 

- Water circulation pump malfunction

 

 

 

CN201

 

 

 

Red

- If Water circulation pump do not start operating even after turning it on on the operation panel, it is a

malfunction of the Water circulation pump.

 

 

- Check if air exists in water

 

 

- If noise of air being

released can be heard when water drain plug or PTR valve is

loosened, remove air.

- Check if the inlet water temperature thermistor is fallen out

 

CN500

 

White

- Put the inlet water temperature thermistor back to the right position if it is out

- Check if the outlet water temperature thermistor is fallen out

 

CN500

 

White

- Put the outlet temperature thermistor back to the right position

if it is out

- Check if the discharge temperature thermistor is fallen out

 

CN500

 

White

- Put the discharge temperature thermistor back to the right position

if it is out

- Check if expansion valve connector is fallen out or not

connected properly

 

CN504

 

White

- Put it back on properly if it is not in right

position

 

- Check resistance between 2 phases on expansion valve coil (see table)

 

 

- Abnormal: Valve coil replacement required (together with PC board)

- Normal: Heat pump unit replacement required

 

 

 

 

 

E008

 

 

 

 

High ambient temperature defrost drive error

Error Detection Condition

Defrost drive conducted while ambient temperature thermistor detected 20 or more

<Check Items>

- Trouble in air absorption due to foreign object blocking air path through evaporator

 

 

 

- Remove foreign object from evaporator

- Ambient temperature thermistor malfunction

CN500

White

- Replace ambient temperatrue thermistor

- defrost temperature thermistor malfunction

CN500

White

- Replace defrost temperatrue thermistor

 

 

Error Code

 

Error Contents

 

Diagnostic

Check Points

 

Judgment & Repair Methods

Connector No. or Maintenance Monitor No.

 

Connector Colour

 

 

 

 

 

 

E009

 

 

 

 

 

HP defrost thermistor detection error

Error Detection Condition

When the defrost temperature thermistor didn't detect ambient temperature thermistor+3 or less during 30 minutes after the compressor operation start

<Check Items>

- Check if the defrost temperature thermistor is fallen out from evaporator

 

CN500

 

White

- Put the defrost temperature thermistor back into the pocket on evaporator if it is out.

 

- malfunction of the defrost temperature thermistor

 

CN500

 

White

 

- Replace the defrost temperature thermistor

 

 

 

E011

 

 

HP inlet temperature thermistor wire break

Error Detection Condition

When the inlet water temperature thermistor detect -30 or less

<Check Items>

 

Refer to Thermistor diagnostic

 

CN500

 

White

 

-Confirm the resistance: (See Table-1 in p.g.17)

 

 

 

E012

 

 

HP outlet temperature thermistor wire break

Error Detection Condition

When the outlet water temperature thermistor detect -30 or less

<Check Items>

 

Refer to Thermistor diagnostic

 

CN500

 

White

-Confirm the resistance: (See Table-1 in p.g.17)

 

 

 

E013

 

 

HP discharge temperature thermistor wire break

Error Detection Condition

When the discharge temperature thermistor detect -31 or less

<Check Items>

 

Refer to Thermistor diagnostic

 

CN500

 

White

-Confirm the resistance: (See Table-3 in p.g.17)

 

 

 

E014

 

HP defrost temperature thermistor wire break

Error Detection Condition

When the defrost temperature thermistor detect -50 or less

<Check Items>

 

Refer to Thermistor diagnostic

 

CN500

 

White

-Confirm the resistance: (See Table-4 in p.g.17)

 

 

 

E015

 

 

HP ambient temperature thermistor wire break

Error Detection Condition

When the Ambient temperature thermistor detect -50 or less

<Check Items>

 

Refer to Thermistor diagnostic

 

CN500

 

White

 

-Confirm the resistance: (See Table-2 in p.g.17)

 

 

 

E016

 

 

Tank thermistor wire break

Error Detection Condition

When the Tank thermistor detect -30     or less

<Check Items>

 

Refer to Thermistor diagnostic

 

CN506

 

White

 

Check to see if it is broken.

 

 

Error Code

 

Error Contents

 

Diagnostic

Check Points

 

Judgment & Repair Methods

Connector No. or Maintenance

Monitor No.

 

Connector Colour

 

 

 

E021

 

HP inlet temperature thermistor wire short circuit

Error Detection Condition

When the inlet water temperature thermistor detect 100 or more

<Check Items>

 

Refer to Thermistor diagnostic

 

CN500

 

White

 

-Confirm the resistance: (See Table-1 in p.g.17)

 

 

 

E022

 

HP outlet temperature thermistor wire short circuit

Error Detection Condition

When the outlet water temperature thermistor detect 150 or more

<Check Items>

 

Refer to Thermistor diagnostic

 

CN500

 

White

-Confirm the resistance: (See Table-1 in p.g.17)

 

 

 

E023

 

HP discharge temperature thermistor wire short circuit

Error Detection Condition

When the discharge temperature thermistor detect 150 or more

<Check Items>

 

Refer to Thermistor diagnostic

 

CN500

 

White

-Confirm the resistance: (See Table-3 in p.g.17)

 

 

 

E024

 

HP defrost temperature thermistor wire short circuit

Error Detection Condition

When the defrost temperature thermistor detect 100 or more

<Check Items>

 

Refer to Thermistor diagnostic

 

CN500

 

White

-Confirm the resistance: (See Table-4 in p.g.17)

 

 

 

E025

 

HP ambient temperature thermistor wire short circuit

Error Detection Condition

When the Ambient temperature thermistor detect 100 or more

<Check Items>

 

Refer to Thermistor diagnostic

 

CN500

 

White

 

-Confirm the resistance: (See Table-2 in p.g.17)

 

 

 

E026

 

 

Tank thermistor short circuit

Error Detection Condition

When the Tank thermistor detect 120     or more

<Check Items>

 

Refer to Thermistor diagnostic

 

CN506

 

White

Check to see if it is shorted.

 

 

 

 

 

 

 

E031

 

 

 

 

 

 

Fan motor locked

Error Detection Condition Continuous fan motor abnormal operation.

<Check Items>

- Fan blade rotated with foreign object stuck on it

 

 

- Remove foreign object

- Fan motor locked

 

 

- Replace fan motor

- Check if connector is fallen out or not connected properly

 

CN200

 

White

- Put it back on properly if it is not in right position

- Fan motor malfunction

CN200

White

- Replace fan motor

 

 

Error Code

 

Error Contents

 

Diagnostic

Check Points

 

Judgment & Repair Methods

Connector No. or Maintenance

Monitor No.

 

Connector Colour

 

 

 

 

 

 

E032

 

 

 

 

 

Fan motor revolution error

Error Detection Condition Continuous fan motor abnormal operation.

<Check Items>

 

-Fan blade do not rotate

 

 

- Put it back on properly if it is not in right position

-Fan blade rotates in higher speed than usual

CN200

White

- Replace fan motor

- Fan motor malfunction

CN200

White

- Replace fan motor

 

 

 

 

 

 

 

 

 

 

E034

 

 

 

 

 

 

 

 

 

Water circulation pump locked

Error Detection Condition

When less than 150rpm of water circulation pump rotation is detected for 20 seconds continuity

<Check Items>

 

- Check if pump connector is fallen out or not connected properly

 

CN201

 

Red

 

- Put it back on properly if it is not in right position

 

 

 

- Water pump malfunction

 

 

 

CN201

 

 

 

Red

- If rotation of water circulation pump do not reach expected number of rotation even after turning it on on the operation panel, it is a malfunction of the water circulation pump.

 

- Check for bends or blockings on HP connection pipes

 

 

 

- Correct piping and remove bends and blockings

 

 

 

 

 

 

 

 

 

 

 

 

 

E041

 

 

 

 

 

 

 

 

 

 

 

 

INV

compressor start error

Error Detection Condition

Compressor start error detected in compressor operation control

<Check Items>

 

 

Error in compressor wiring

 

 

- confirm connection of wire terminals to compressor is in the right order

 

- Error in connection on power supply terminal block

 

 

- Confirm cable is connected correctly at terminal block

 

- Power supply voltage error

 

 

- Confirm power supply voltage (187 254 V (include tolerance))

 

 

- PC Board malfunction

 

 

- PCB replacement required if same error occurs again after re-run of heat pump

 

- Compressor malfunction

 

 

 

- Heat pump unit replacement required

 

 

Error Code

 

Error Contents

 

Diagnostic

Check Points

 

Judgment & Repair Methods

Connector No. or Maintenance

Monitor No.

 

Connector Colour

 

 

 

 

 

 

 

 

 

E042

 

 

 

 

 

 

 

 

INV

communicatio n error

Error Detection Condition

Communication error detected in compressor operation control

<Check Items>

 

- Wiring layout is not following instruction

 

 

 

- Confirm connector connections

 

 

- noise source is near harnesses

 

 

 

- Stop operation of all the surrounding electrical products and reboot Heat Pump

 

 

- PC board malfunction

 

 

- PCB replacement required if same error occurs again after re-run of heat pump

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INV transient over-current error on hardware (converter)

Error Detection Condition

Over current error detected in compressor operation control

<Check Items>

- Check for HP control PC board connector connection

 

 

- Confirm connector connections

 

 

- Error in compressor wiring

 

 

- confirm connection of wire terminals to compressor is in the right order

 

- Error in connection on power supply terminal block

 

 

- Confirm cable is connected correctly at terminal block

- Check dust being stuck on HP connector

 

 

- Remove dust

- Bends or blockings and freeze on HP connection pipes

 

 

-Correct piping and

remove bends and blockings

 

- Stopper valve is closed

 

 

 

- Open stopper valve

 

- Air exists in water pipe

 

 

 

- Remove air

 

- Water circulation pump malfunction

 

 

- Conduct operation check on water circulation pump

 

- Power cutoff occurred

 

 

- Check Power supply cable wiring layout

 

- Power supply voltage error

 

 

- Confirm power supply voltage (187 254 V (include tolerance))

 

 

- PC board malfunction

 

 

 

-     PCB replacement required if same error occurs again after re-run of heat pump

 

 

Error Code

 

Error Contents

 

Diagnostic

Check Points

 

Judgment & Repair Methods

Connector No. or Maintenance

Monitor No.

 

Connector Colour

 

 

Error Detection Condition

 

 

Over current error detected in compressor operation control

 

 

<Check Items>

 

 

 

- Check for HP control PC board connector connection

 

 

 

- Confirm connector connections

 

 

 

 

- Error in compressor wiring

 

 

 

- confirm connection of wire terminals to compressor is in the right order

 

 

 

- Error in connection on power supply terminal block

 

 

 

- Confirm cable is connected correctly at terminal block

 

 

 

- Check dust being stuck on HP connector

 

 

 

- Remove dust

 

 

 

- Bends or blockings and freeze on HP connection pipes

 

 

 

-Correct piping and remove bends and blockings

 

 

E051

INV transient over-current error on hardware (inverter)

 

 

 

- Stopper valve is closed

 

 

 

- Open stopper valve

 

 

 

 

 

 

- Air exists in water pipe

- Remove air

 

 

 

 

- Water circulation pump malfunction

 

 

 

 

- Conduct operation check on water circulation pump

 

 

 

 

- Power cutoff occurred

 

 

 

 

- Check Power supply cable wiring layout

 

 

 

 

 

 

- Confirm power supply

 

 

- Power supply voltage error

voltage (187  254 V

 

 

 

(include tolerance))

 

 

 

 

 

- PC board malfunction

 

 

 

 

- PCB replacement required if same error occurs again after re-run of heat pump

 

 

Error Code

 

Error Contents

 

Diagnostic

Check Points

 

Judgment & Repair Methods

Connector No. or Maintenance

Monitor No.

 

Connector Colour

 

 

Error Detection Condition

 

 

Over current error detected in compressor operation control

 

 

<Check Items>

 

 

 

- Check for HP control PC board connector connection

 

 

 

- Confirm connector connections

 

 

 

 

- Error in compressor wiring

 

 

 

- confirm connection of wire terminals to compressor is in the right order

 

 

 

- Error in connection on power supply terminal block

 

 

 

- Confirm cable is connected correctly at terminal block

 

 

 

- Check dust being stuck on HP connector

 

 

 

- Remove dust

 

 

 

 

 

 

E052

 

 

 

 

INV transient over-current error on software (inverter)

 

 

- Bends or blockings and freeze on HP connection pipes

 

 

 

-Correct piping and remove bends and blockings

 

- Stopper valve is closed

 

 

 

- Open stopper valve

 

 

 

- Air exists in water pipe

 

 

 

- Remove air

 

 

 

 

- Water circulation pump malfunction

 

 

 

- Conduct operation check on water circulation pump

 

 

 

 

- Power cutoff occurred

 

 

 

- Check Power supply cable wiring layout

 

 

 

 

 

 

- Confirm power supply

 

 

- Power supply voltage error

voltage (187  254 V

 

 

 

(include tolerance))

 

 

 

 

 

 

- PC board malfunction

 

 

 

- PCB replacement required if same error occurs again after re-run of heat pump

 

 

Error Code

 

Error Contents

 

Diagnostic

Check Points

 

Judgment & Repair Methods

Connector No. or Maintenance

Monitor No.

 

Connector Colour

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E053

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INV transient over-current error on software (converter)

Error Detection Condition

Over current error detected in compressor operation control

<Check Items>

- Check for HP control PC board connector connection

 

 

- Confirm connector connections

 

 

- Error in compressor wiring

 

 

- confirm connection of wire terminals to compressor is in the right order

 

- Error in connection on power supply terminal block

 

 

- Confirm cable is connected correctly at terminal block

- Check dust being stuck on HP connector

 

 

- Remove dust

 

- Bends or blockings and freeze on HP connection pipes

 

 

-Correct piping and remove bends and blockings

 

- Stopper valve is closed

 

 

 

- Open stopper valve

 

- Air exists in water pipe

 

 

 

- Remove air

 

- Water circulation pump malfunction

 

 

- Conduct operation check on water circulation pump

 

- Power cutoff occurred

 

 

- Check Power supply cable wiring layout

 

- Power supply voltage error

 

 

- Confirm power supply voltage (187 254 V (include tolerance))

 

 

- PC board malfunction

 

 

- PCB replacement required if same error occurs again after re-run of heat pump

 

 

 

 

 

 

 

E054

 

 

 

 

 

 

INV

temperature sensor error

Error Detection Condition

Wire break or short circuit detected on thermistor in HP control PC board

<Check Items>

 

- Thermistor wiring error

 

CN500

 

White

- Confirm connector connections

 

 

- malfunction of thermistor on HP control PC board

 

 

 

- PCB replacement required if same error occurs again after re-run of heat pump

 

 

Error Code

 

Error Contents

 

Diagnostic

Check Points

 

Judgment & Repair Methods

Connector No. or Maintenance

Monitor No.

 

Connector Colour

 

 

 

 

 

 

 

 

 

E055

 

 

 

 

 

 

 

 

INV heatsink temperature error

Error Detection Condition

90degC or more detected by thermistor on HP control PC board

<Check Items>

 

 

- No fan blade rotation

 

 

- Check fan motor rotation

 

 

- Confirm connector connections

 

 

 

- No efficient air absorption amount

 

 

 

- Check if any damege on propellar fan blade

 

 

 

- Remove foreign object from evaporator if any

- Fan motor malfunction

 

 

- Replace fan motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E056

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INV overload detection error

Error Detection Condition

Overload Detected in compressor operation control

<Check Items>

- Check for HP control PC board connector connection

 

 

- Confirm connector connections

 

- Compressor wiring error

 

 

- confirm connection of wire terminals to compressor is in the right order

- Error in connection on power supply terminal block

 

 

- Confirm wire connection on terminal block.

- Check dust being stuck on HP connector

 

 

- Remove foreign object if any

 

- Bends or blockings and freeze on HP connection pipes

 

 

-Correct piping and remove bends and blockings

- Check if stopper valve is open

 

 

- Open stopper valve

- Air exists in water pipe

 

 

- Remove air

- Water circulation pump malfunction

 

 

- Conduct operation check on water circulation pump

 

- Power cutoff occurred

 

 

- Check Power supply cable wiring layout

 

- Power supply voltage error

 

 

- Confirm power supply voltage (187 254 V (include tolerance))

 

 

- PC board malfunction

 

 

- PCB replacement required if same error occurs again after re-run of heat pump

 

 

Error Code

 

Error Contents

 

Diagnostic

Check Points

 

Judgment & Repair Methods

Connector No. or Maintenance

Monitor No.

 

Connector Colour

 

 

 

 

 

 

 

 

 

 

 

E057

 

 

 

 

 

 

 

 

 

 

INV power supply low- voltage error

Error Detection Condition

Power supply voltage drop detected in compressor operation control

<Check Items>

- Check for HP control PC board connector connection

 

 

- Confirm connector connections

 

- Error in compressor wiring

 

 

- confirm connection of wire terminals to compressor is in the right order

- Error in connection on power supply terminal block

 

 

- Confirm cable is

connected correctly at terminal block

 

- Power cutoff occurred

 

 

- Check Power supply cable wiring layout

 

- Power supply voltage error

 

 

- Confirm power supply voltage (187 254 V

(include tolerance))

 

- PC board malunction

 

 

- PCB replacement required if same error occurs again after re-run of heat pump

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E058

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INV Power Supply Over- Voltage Error

Error Detection Condition

Over voltage error detected in compressor operation control

<Check Items>

- Check for HP control PC board connector connection

 

 

- Confirm connector connections

 

- Error in compressor wiring

 

 

- confirm connection of wire terminals to

compressor is in the right order

- Error in connection on power supply terminal block

 

 

- Confirm cable is connected correctly at terminal block

- Check dust being stuck on HP connector

 

 

- Remove dust

 

- Bends or blockings and freeze on HP connection pipes

 

 

-Correct piping and remove bends and blockings

- Stopper valve is closed

 

 

- Open stopper valve

- Air exists in water pipe

 

 

- Remove air

- Water circulation pump malfunction

 

 

- Conduct operation

check on water circulation pump

 

- Power cutoff occurred

 

 

- Check Power supply cable wiring layout

 

- Power supply voltage error

 

 

- Confirm power supply voltage (187 254 V (include tolerance))

 

 

- PC board malfunction

 

 

- PCB replacement required if same error occurs again after re-run of heat pump

 

 

Error Code

 

Error Contents

 

Diagnostic

Check Points

 

Judgment & Repair Methods

Connector No. or Maintenance

Monitor No.

 

Connector Colour

 

 

 

 

 

 

 

 

E059

 

 

 

 

 

 

 

INV serial communicatio n error

Error Detection Condition

Error detected on serial communication driver

<Check Items>

Error in compressor wiring

 

 

- Correct compressor wiring

 

 

 

- Check resistance between 2 phases on compressor

 

 

 

- Normal: PC board replacement required

 

 

- Abnormal: Heat pump unit replacement required

compressor malfunction

 

 

- Heat pump unit replacement required

 

 

 

 

E060

 

 

INV Inverter Current Detection Circuit Error

Error Detection Condition Error detected inside PC board

<Check Items>

 

 

- PC Board malfunction

 

 

- PCB replacement required if same error occurs again after re-run of heat pump

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E061

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INV transient power cutoff detection error 1

Error Detection Condition

Power cutoff detected in compressor operation control

<Check Items>

- Check for HP control PC board connector connection

 

 

- Confirm connector connections

 

 

- Error in compressor wiring

 

 

- confirm connection of wire terminals to compressor is in the right order

 

- Error in connection on power supply terminal block

 

 

- Confirm cable is connected correctly at terminal block

 

- Power cutoff occurred

 

 

- Check Power supply cable wiring layout

 

 

- Power supply voltage error

 

 

 

- Confirm power supply voltage (187 254 V (include tolerance))

 

 

 

 

- PC board malfunction

 

 

 

 

- PCB replacement required if same error occurs again after re-run of heat pump

 

 

Error Code

 

Error Contents

 

Diagnostic

Check Points

 

Judgment & Repair Methods

Connector No. or Maintenance

Monitor No.

 

Connector Colour

 

 

 

 

 

 

 

 

 

 

 

 

 

E062

 

 

 

 

 

 

 

 

 

 

 

 

INV transient power cutoff detection error 2

Error Detection Condition

Power cutoff detected in compressor operation control

<Check Items>

- Check for HP control PC board connector connection

 

 

- Confirm connector connections

 

 

- Error in compressor wiring

 

 

- confirm connection of wire terminals to compressor is in the right order

 

- Error in connection on power supply terminal block

 

 

- Confirm cable is connected correctly at terminal block

 

- Power cutoff occurred

 

 

- Check Power supply cable wiring layout

 

- Power supply voltage error

 

 

- Confirm power supply voltage (187 254 V (include tolerance))

 

- PC board malfunction

 

 

- PCB replacement required if same error occurs again after re-run of heat pump

 

 

 

 

E063

 

 

INV control circuit board power supply error

Error Detection Condition Error detected inside PC board

<Check Items>

 

- PC Board malfunction

 

 

- PCB replacement required if same error occurs again after re-run of heat pump

 

 

 

 

 

 

 

 

 

 

 

E064

 

 

 

 

 

 

 

 

 

 

INV transient voltage drop detection error

Error Detection Condition

Power cutoff detected in compressor operation control

<Check Items>

- Check for HP control PC board connector connection

 

 

- Confirm connector connections

 

- Error in compressor wiring

 

 

- confirm connection of wire terminals to

compressor is in the right order

- Error in connection on power supply terminal block

 

 

- Confirm cable is connected correctly at terminal block

 

- Power cutoff occurred

 

 

- Check Power supply cable wiring layout

 

- Power supply voltage error

 

 

- Confirm power supply

voltage (187 254 V (include tolerance))

 

- PC board malfunction

 

 

- PCB replacement required if same error occurs again after re-run of heat pump

 

 

Error Code

 

Error Contents

 

Diagnostic

Check Points

 

Judgment & Repair Methods

Connector No. or Maintenance

Monitor No.

 

Connector Colour

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E065

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INV motor operation detection error

Error Detection Condition Compressor rotation error was detected

<Check Items>

- Check for HP control PC board connector connection

 

 

- Confirm connector connections

- Trouble in air absorption due to foreign object blocking air path through evaporator

 

 

- Remove foreign object from evaporator if any

- Check dust being stuck on HP connector

 

 

- Remove foreign object if any

 

- Bends or blockings and freeze on HP connection pipes

 

 

-Correct piping and remove bends and blockings

- Stopper valve is closed

 

 

- Open stopper valve

- Air exists in water pipe

 

 

- Remove air

 

- Water circulation pump malfunction

 

 

- Conduct operation check on water circulation pump

 

- Compressor wiring error

 

 

- confirm connection of wire terminals to compressor is in the right order

- Power cutoff occurred

 

 

- Check Power supply cable wiring layout

 

- Power supply voltage error

 

 

- Confirm power supply voltage (187 254 V (include tolerance))

 

- Error in connection on power supply terminal block

 

 

 

- Confirm wire connection on terminal block.

 

 

- PC board malfunction

 

 

 

- PCB replacement required if same error occurs again after re-run of heat pump

 

 

 

 

 

 

E066

 

 

 

 

INV Converter Current detection Circuit Error

Error Detection Condition Error detected inside PC board

<Check Items>

 

 

 

 

- PC Board malfunction

 

 

 

 

- PCB replacement required if same error occurs again after re-run of heat pump

 

 

Error Code

 

Error Contents

 

Diagnostic

Check Points

 

Judgment & Repair Methods

Connector No. or Maintenance Monitor No.

 

Connector Colour

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E080

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outlet water temperture rise error

Error Detection Condition Continuous water pump abnormal operation.

<Check Items>

- Check on HP connector

 

 

- Remove dust if any

- Bends or blockings on HP connection pipes

 

 

-Correct piping and remove bends and blockings

 

- freeze on pipes

 

 

- Check temperature on pipe cover that is exposed to ambient temperature

- Water valve is closed

 

 

- Open water valve

- Stopper valve is closed

 

 

- Open stopper valve

- confirm tank is filled

 

 

- fill tank with water if it is not

 

 

- Water circulation pump malfunction

 

 

- If Water circulation pump do not start operating even after turning it on on the operation panel, it is a malfunction of the water circulation pump.

 

 

- Check if air exists in water

 

 

- If noise of air being released can be heard when water drain plug or PTR valve is loosened, remove air.

 

- Check if the inlet water temperature thermistor is fallen out

 

 

- Put the inlet water temperature thermistor back to the right position if it is out

 

- Check if the outlet water temperature thermistor is fallen out

 

 

- Put the outlet temperature thermistor back to the right position if it is out

 

- Check if the discharge temperature thermistor is fallen out

 

CN500

 

White

- Put the discharge temperature thermistor back to the right position if it is out

 

- Check if expansion valve connector is fallen out or not connected properly

 

 

CN504

 

 

White

 

- Put it back on properly if it is not in right position

 

 

 

- Check resistance between 2 phases on expansion valve coil (see table)

 

 

- Abnormal: Valve coil replacement required (together with PC board)

- Normal: Heat pump unit replacement required

 

 

Error Code

 

Error Contents

 

Diagnostic

Check Points

 

Judgment & Repair Methods

Connector No. or Maintenance

Monitor No.

 

Connector Colour

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E081

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor overload protection

Error Detection Condition

Current error detected in compressor operation control

<Check Items>

 

 

- Check for HP control PC board connector connection

 

 

 

 

- Confirm connector connections

 

 

- Error in compressor wiring

 

 

 

- confirm connection of wire terminals to compressor is in the right order

 

- Error in connection on power supply terminal block

 

 

 

- Confirm cable is connected correctly at terminal block

 

- Check dust being stuck on HP connector

 

 

 

- Remove dust

 

- Bends or blockings and freeze on HP connection pipes

 

 

 

-Correct piping and remove bends and blockings

 

- Stopper valve is closed

 

 

 

- Open stopper valve

 

- Air exists in water pipe

 

 

 

- Remove air

 

 

- Water circulation pump malfunction

 

 

 

- Conduct operation check on water circulation pump

 

 

- Power cutoff occurred

 

 

 

- Check Power supply cable wiring layout

 

 

- Power supply voltage error

 

 

 

- Confirm power supply voltage (187 254 V (include tolerance))

 

 

 

- PC board malfunction

 

 

 

-     PCB replacement required if same error occurs again after re-run of heat pump

 

 

Error Code

 

Error Contents

 

Diagnostic

Check Points

 

Judgment & Repair Methods

Connector No. or Maintenance

Monitor No.

 

Connector Colour

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E082

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor low-current protection

Error Detection Condition

Current error detected in compressor operation control

<Check Items>

 

- Check for HP control PC board connector connection

 

 

 

- Confirm connector connections

 

 

- Error in compressor wiring

 

 

 

- confirm connection of wire terminals to compressor is in the right order

 

- Error in connection on power supply terminal block

 

 

 

- Confirm cable is connected correctly at terminal block

- Check dust being stuck on HP connector

 

 

- Remove dust

 

- Bends or blockings and freeze on HP connection pipes

 

 

 

-Correct piping and remove bends and blockings

- Stopper valve is closed

 

 

- Open stopper valve

 

- Air exists in water pipe

 

 

 

- Remove air

 

- Water circulation pump malfunction

 

 

 

- Conduct operation check on water circulation pump

 

- Power cutoff occurred

 

 

 

- Check Power supply cable wiring layout

 

 

 

- Power supply voltage error

 

 

 

 

- Confirm power supply voltage (187 254 V (include tolerance))

 

 

 

 

- PC board malfunction

 

 

 

 

-     PCB replacement required if same error occurs again after re-run of heat pump

 


loading
1300 86 78 73
Reviews
Products Review Pure-Electric

Product Review Rating

5.0
Based on 80 reviews
Google Review Pure-Electric

Google Review Rating

4.9
Based on 84 reviews
Trustpilot Review Pure-Electric

Trustpilot Rating

4.9
Based on 106 reviews
Wordofmouth Review Pure-Electric

Word of Mouth Rating

5.0
Based on 16 reviews
Facebook Review Pure-Electric

Facebook Rating

5.0
Based on 9 reviews