Fronius Reserva Changelog v1.4.0-0 May2025
Description
Changelog RESERVA
Fronius International May 28, 2025
Version: 1.4.0-0
2.1 RESERVA
2.1.1 Bundle 1.4.0-0
New features
/ Inverter can check for serial number of the battery.
/ Increase of the overvoltage protection threshold to 608V (3.8V*32 cells*5 modules).
/ Some data is stored in the module to prevent data loss in case of a BMS change.
Bugfixes
/ Fix the software bug: For every fault that needs to open the DC-breaker, the software would only shut off the BMS without opening the DC-breaker. While for every fault that needs to only shut off the BMS, the breaker would open.
/ Fix various software bugs.
/ Fix timestamp errors of various registers.
/ Fix bugs in the position of faults in the fault buffer.
/ Fix the resolution of a register.
/ Fix various software bugs.
/ Fix the level 3 fault report through the fault buffer issue.
/ Fix the addressing fault in parallel mode due to timeout issue.
/ Fix the synchronizing fault of the stack flag which is set in the one-tower application.